| Hubbell Wiring Device-Kellems Product
Specifications |
| Hospital Product Type |
|
| Amperage |
15A |
| Voltage |
125V |
| Color |
|
| NEMA Number |
5-15 |
| Horsepower |
0.5 |
| Input |
Power cord 6' (182.9 cm) |
| Duplex Receptacles |
3 |
| Circuit Breaker |
Yes |
| On/Off Switch |
Yes |
| Surge LED |
Yes |
| Status Alarm |
Yes |
| Dimension H |
15.75" (400.0) |
| Dimension W |
2.25" (57.2) |
| Dimension D |
1.16" (29.5) |
| Description |
Hospital Grade Multi Outlet
Strip |
| Type |
2 Pole, 3 Wire, Grounding
|
| Certification |
Listed to UL Standard 498.
Certified to CSA 22.2, No. 42 where applicable. |
| Dielectric Voltage |
Withstands 2,000V minimum.
|
| Response Time |
Approx. 5 ns |
| Input Voltage |
125V AC (60Hz) |
| Current |
20A Max Branch Circuit |
| Protection Modes |
Normal and Common |
| Transient Suppression at Peak
Energy (10 x 1000 µs) |
140 Joules per mode |
| Transient Suppression at Peak
Current (8 x 20 µs) |
13000A |
| UL Portable/Plug-In Test (8x20
µs 500A) Suppressed Voltage |
330V |
| Telecom Circuit Suppressed
Voltage |
200V max |
| Current Interrupting |
Certified for current
interrupting at full rated current. |
| Temperature Rise |
Max 30 deg C temperature rise
at full rated current after 50 cycles of overload at 150% of rated
current with direct current |
| Normal EMI/RFI Rejection (@50
Ohms) |
Up to 80dB 150kHz to 100 MHz
|
| Common EMI/RFI Rejection (@50
Ohms) |
Up to 60 dB |
| Terminal Identification |
Terminals identified in
accordance with UL498 (Brass, White, Green). |
| Product Identification |
Ratings are a permanent part of
the device. |
| Flammability |
UL 94 V0 and UL 94-5 VA. |
| Operating Temperatures |
Maximum continuous 75°C,
minimum -40°C (w/o impact). |
| Storage Temperature |
-35° to +60° C (-31° to +140°
F) |